Status: this pinout is less well confirmed than Deye, Solis and Hoymiles. For the T-REX-10KLP3G01 we only have the German manual, and none for the 15 kW model. Before you connect, compare it with the label printed next to the connector on your inverter.
T-REX-10KLP3G01 and T-REX-15KLP3G01 (three-phase, 48 V battery)
Which connector
The COM connector underneath the inverter (no. 11 in the manual’s overview drawing). According to the manual it is a six-position terminal block, not an RJ45 socket. RS485-3 (manual: “zum Debuggen”, for monitoring) is meant for external devices; RS485-2 serves the energy meter.
| Position | Signal (Felicity) | Manufacturer note | Dongle terminal |
|---|---|---|---|
| 1 | RY1_4 | dry contact | – |
| 2 | RY1_5 | dry contact | – |
| 3 | RS485_B3 | RS485-3 | B |
| 4 | RS485_A3 | RS485-3 | A |
| 5 | RS485_A2 | RS485-2, meter | – |
| 6 | RS485_B2 | RS485-2, meter | – |
🟡 Source: Benutzerhandbuch T-REX-10KLP3G01 (358-S010004-01), table 4.4-1. Uncertain:
- the connector type and the order of positions on the block are read off a drawing, not stated in text;
- the English manual on Felicity’s site was not reachable for us;
- we found no manual for the T-REX-15KLP3G01 and assume the same layout as the 10K.
Positions 5 and 6 are used by the meter shipped with the inverter: do not connect the dongle there.
T-REX HP (high voltage, e.g. T-REX-50KHP3G01)
The RJ45 port labelled RS485 underneath the inverter.
| Pin | Signal (Felicity) | Manufacturer note | Dongle terminal |
|---|---|---|---|
| 1 | 485_A2 | RS485-2, meter | – |
| 2 | 485_B2 | RS485-2, meter | – |
| 3 | 485_A3 | RS485-3, remote monitoring | A |
| 4 | 485_B3 | RS485-3, remote monitoring | B |
| 5 | 485_B3 | RS485-3 (repeated) | – |
| 6 | 485_A3 | RS485-3 (repeated) | – |
| 7 | RY_4 | dry contact | – |
| 8 | RY_5 | dry contact | – |
🟡 Source: the manufacturer’s table reproduced on Solar Assistant’s pages (T-REX-50KHP3G01, IVGM). Note: Solar Assistant’s text says “pin 5 RS485A, pin 6 RS485B”, while the manufacturer’s table on the same page says the opposite (5 = B3, 6 = A3). Use pins 3 and 4, which agree in both places. Whether the T-REX-10KHP3G01 uses the same layout: ⚠️ not verified.
How Felicity draws the connector
Felicity draws the socket latch up, numbered 8…1 from the left, and the plug in perspective numbered 8…1. That is geometrically right (pin 1 is on the right when the latch is on top), but easy to confuse with Deye’s or Solis’s drawings, where the latch is at the bottom and pin 1 on the left. Our plug drawing converts it to the common site convention.
Sources
- Felicity, Benutzerhandbuch Hybrid-Solarwechselrichter T-REX-10KLP3G01 (358-S010004-01): PDF (solarscouts.de)
- Solar Assistant: Felicity T-REX 50kW HP RS485, IVGM RS485